冷庫制冷系統加入制冷劑時一(yi)定要保證制(zhi)冷(leng)(leng)劑的(de)干燥(僅適用于氟制(zhi)冷(leng)(leng)劑制(zhi)冷(leng)(leng)系(xi)(xi)統(tong)),不(bu)然制(zhi)冷(leng)(leng)系(xi)(xi)統(tong)一(yi)定會因為(wei)(wei)制(zhi)冷(leng)(leng)劑的(de)不(bu)干燥,造成制(zhi)冷(leng)(leng)系(xi)(xi)統(tong)冰堵,從而影響制(zhi)冷(leng)(leng)系(xi)(xi)統(tong)的(de)正常運作,下面(mian)就來(lai)為(wei)(wei)大(da)家詳(xiang)細的(de)說明一(yi)下氟制(zhi)冷(leng)(leng)系(xi)(xi)統(tong)中制(zhi)冷(leng)(leng)劑的(de)充注(zhu)與排放。
制(zhi)冷系統(tong)在(zai)補充制(zhi)冷劑時,要關閉(bi)冷凝器或儲液(ye)(ye)器的(de)出液(ye)(ye)閥,把輸(shu)液(ye)(ye)管和低壓(ya)系統(tong)抽真(zhen)空,停(ting)機(ji),關閉(bi)排氣閥,微開(kai)出液(ye)(ye)閥,使低壓(ya)系統(tong)壓(ya)力回升至0MPa。
拆下干燥過濾器,更換新干燥劑重新裝上,再次將輸液管和低壓系統抽真空,然后開啟排氣閥,出液閥,截止閥,啟動壓縮機,運動數小時。
重(zhong)復上述(shu)操作,檢查更換(huan)干燥(zao)劑直(zhi)至制冷劑中沒有水分(fen)為止。
制冷劑的補充
1.系(xi)(xi)統(tong)補充(chong)氨(an)(an)。氨(an)(an)系(xi)(xi)統(tong)一般都設置加氨(an)(an)閥(fa),用(yong)于氨(an)(an)液(ye)補充(chong)。加液(ye)操(cao)(cao)作時先(xian)關(guan)閉(bi)總(zong)調節(jie)站上來自儲(chu)液(ye)器(qi)(qi)(qi),中(zhong)間(jian)冷(leng)卻器(qi)(qi)(qi),排液(ye)器(qi)(qi)(qi)的(de)(de)供液(ye)閥(fa),啟(qi)動(dong)壓縮機,降(jiang)低(di)蒸(zheng)發系(xi)(xi)統(tong)的(de)(de)壓力,開啟(qi)氨(an)(an)瓶閥(fa),加氨(an)(an)閥(fa),氨(an)(an)液(ye)通過加液(ye)管進(jin)入(ru)蒸(zheng)發器(qi)(qi)(qi)和循環儲(chu)液(ye)器(qi)(qi)(qi),然后(hou)被壓縮機吸入(ru),最后(hou)進(jin)入(ru)儲(chu)液(ye)器(qi)(qi)(qi)。加液(ye)過程(cheng)中(zhong)必須遵(zun)守(shou)設備安全操(cao)(cao)作規程(cheng)的(de)(de)規定(ding),加液(ye)后(hou)的(de)(de)儲(chu)液(ye)器(qi)(qi)(qi)存液(ye)量(liang)不得超過儲(chu)液(ye)器(qi)(qi)(qi)容積(ji)的(de)(de)80%。
2.系(xi)統補充氟化合(he)物。大,中(zhong)型氟化合(he)物系(xi)統一般在(zai)高壓側(ce)設(she)置加液(ye)閥。加液(ye)操(cao)作(zuo)時加液(ye)管連(lian)接(jie)制(zhi)(zhi)冷(leng)劑鋼瓶和加液(ye)閥,排(pai)除加液(ye)管內的(de)空氣(qi)后(hou)旋緊接(jie)管螺母,然后(hou)關閉儲(chu)液(ye)器(qi)的(de)供(gong)液(ye)閥,開啟加液(ye)閥,使(shi)鋼瓶內的(de)制(zhi)(zhi)冷(leng)劑靠壓力差和高度(du)差自(zi)行(xing)(xing)(xing)進(jin)入系(xi)統。加液(ye)時應使(shi)用磅秤進(jin)行(xing)(xing)(xing)計量(liang),并(bing)通(tong)過儲(chu)液(ye)器(qi)上的(de)液(ye)位(wei)指示器(qi)觀察,控(kong)(kong)制(zhi)(zhi)加液(ye)量(liang)。小(xiao)型氟化合(he)物系(xi)統不(bu)設(she)加液(ye)閥,只能通(tong)過壓縮(suo)機吸(xi)氣(qi)閥多用通(tong)道(dao)或工藝管在(zai)開機狀態下進(jin)行(xing)(xing)(xing)補充制(zhi)(zhi)冷(leng)劑操(cao)作(zuo)。為避免壓縮(suo)機“來(lai)霜”產生液(ye)擊(ji),必須(xu)控(kong)(kong)制(zhi)(zhi)制(zhi)(zhi)冷(leng)劑鋼瓶閥門的(de)開啟度(du),保證吸(xi)入的(de)是制(zhi)(zhi)冷(leng)劑氣(qi)體,補充量(liang)的(de)控(kong)(kong)制(zhi)(zhi)應稱重(zhong)計算,或是從制(zhi)(zhi)冷(leng)系(xi)統的(de)運行(xing)(xing)(xing)狀況來(lai)分析判斷。
制冷劑的排放
在制冷(leng)系統(tong)進行設備大修時,應把制冷(leng)劑從(cong)系統(tong)中排入儲(chu)液鋼瓶內,其方(fang)法(fa)有如下(xia)兩種:
大,中(zhong)型設備可(ke)通過(guo)系統(tong)的(de)(de)加液(ye)閥于(yu)空(kong)鋼(gang)(gang)瓶(ping)連接(jie),將鋼(gang)(gang)瓶(ping)抽成真(zhen)空(kong)后,利(li)用習慣于(yu)鋼(gang)(gang)瓶(ping)的(de)(de)壓差作用,使(shi)儲液(ye)器內(nei)的(de)(de)制冷劑液(ye)體流入鋼(gang)(gang)瓶(ping)。放液(ye)過(guo)程(cheng)中(zhong)要將鋼(gang)(gang)瓶(ping)置于(yu)磅秤(cheng)上,隨(sui)時注意加入鋼(gang)(gang)瓶(ping)內(nei)的(de)(de)制冷劑質量不得超(chao)過(guo)允許的(de)(de)充裝量。
小(xiao)型系統可利用自身的壓(ya)(ya)(ya)縮機(ji)(ji)(ji)年或(huo)(huo)者借用另一(yi)臺壓(ya)(ya)(ya)縮機(ji)(ji)(ji)來(lai)抽取制(zhi)冷劑(ji),操作(zuo)時將壓(ya)(ya)(ya)縮機(ji)(ji)(ji)排(pai)氣(qi)管(guan)或(huo)(huo)排(pai)氣(qi)閥多(duo)用通(tong)道于鋼(gang)瓶連接,在鋼(gang)瓶外(wai)不斷淋(lin)澆自來(lai)水(shui),啟動壓(ya)(ya)(ya)縮機(ji)(ji)(ji),將系統中的制(zhi)冷劑(ji)壓(ya)(ya)(ya)入鋼(gang)瓶并冷卻成液體。操作(zuo)中要注意控制(zhi)排(pai)氣(qi)壓(ya)(ya)(ya)力,必要時可關小(xiao)壓(ya)(ya)(ya)縮機(ji)(ji)(ji)吸氣(qi)閥,以降(jiang)低排(pai)氣(qi)壓(ya)(ya)(ya)力。 |